Frames for Eliminators & Louvers |
|
Corrosion
free frames for eliminators and louvers for use in Air
washers, Humidification plants, Ventilation systems,
Air handling units, Cooling towers and such diverse
applications to serve Textile, Cement, Power, Coal and
many other industries.
All load-bearing M.S. material is completely encased
by PVC, thereby avoiding costly surface treatment
processes like Hot Dipped Galvanizing. As the existing
system of fixing with M.S. angles is maintained, there
is no change in the manner in which eliminators and
louvers are being installed at present. Design has
been modified to discard bolting requirements wherever
possible. |
|
Frames for Eliminators
: Wall Mounted |
 |
|
A complete eliminator
frame has following configuration: |
- A pair of stiffeners with spacer bar / notch
plate with wall bracket for top (touching the
ceiling). These acts like Z- sections used in
eliminator frames made of metal. If the ceiling is
uneven, the top of stiffener can be filled with
cement.
- Required pairs of stiffeners with spacer bar /
notch plate with wall brackets for middle supports -
number of supports is calculated in such a way that
there is a horizontal support at not more than 1500
mm of vertical height of eliminator.
- A pair of bottom angles (if required by
customer) for supporting eliminators at bottom, if
there is no continuous support.
- Tie bars for all pairs of stiffeners, at
approximately 1500 mm of eliminator width. Tie bars
have same shape as eliminators.
- A pair of side water seals having Z shape. These
are to be nailed to side walls outside the
eliminators, to prevent escape of water from the
sides.
|
|
A packing list will give details of all material
supplied for the frame. |
|
|
|
Frames for Eliminators
: Box Type |
 |
|
A complete box type
eliminator frame has following configuration: |
- A rectangle made of stiffeners with spacer bar
for use at top. This will hold eliminators at top
and will also form sealing mechanism at top to
prevent seepage of water.
- A rectangle made of stiffeners with spacer bar
for use at bottom. This also provides support to
eliminators at bottom.
- Required number of additional horizontal
supports for holding eliminators at middle. Number
of horizontal supports are calculated in such a way
that vertical distance between horizontal supports
is not more than 1500 mm.
- Tie bars for middle pairs of stiffeners, at
approximately 1500 mm of eliminator width. Tie bars
have same shape as eliminators.
- L shaped holdfasts for fixing the box to the
wall.
- A pair of side water seals having Z shape. These
are to be nailed to side walls outside the
eliminators, to prevent escape of water from the
sides.
|
|
A packing list will give details of all material
supplied for the frame. |
|
|
|
Frames for Louvers |
|
A complete louver frame
has following configuration: |
 |
-
Required number of horizontal stiffeners for
grouting into side walls. There is one horizontal
stiffener around 300 mm from the top, one around 300
mm from the bottom and more if required, to maintain
a distance of not more than 1300 mm vertically.
-
Holdfasts and bolts for fixing stiffeners to
side walls.
-
A G channel with slots for louvers for right
hand side, a G channel for left hand side and
required number of middle G channels, to maintain a
distance of not more than 800 mm between two
vertical G channels.
-
Clamps for bolting G channels to horizontal
stiffeners with required bolts.
-
Vertical PVC strips which are bolted to vertical
G channels, to act as stoppers, to stop louvers from
coming out of slots, once fitted.
|
|
We provide a packing list of the components supplied
along with distances at which horizontal stiffeners
are to be fixed to side walls. |